::Very simple 3 step procedure ::
Applications and Industries: Industrial process waters, boiler water, cooling waters
Chemistry: Results are expressed in ppm (mg/L) sodium nitrite (NaNO2).
The method is free from glycol interference in samples that contain up to 75% glycol, making it particularly applicable to systems that contain nitrite corrosion inhibitors. Results are expressed as ppm (mg/L) NaNO2.
PROCEDURE for test ( STEP WISE ):
- Measure 1 ml of SAMPLE WATER in graduated TEST TUBE / CYLINDER , with the help of syringe / pippet and diluted with Distilled Water up to 10 ml.
- Add 1-2 drops of RXSOL TK5 and mix with the stirring rod , to obtain ORANGE / light reddish colour.
-
Add RXSOL TK6 drop by drop , mixing with the stirring rod until For endpoint ORANGE to BLUE / GREENISH colour just appears / develop.
Each DROPS is equivalent to 50 PPM of NO2
CALCULATION : 50 X Number of DROPS of TK6
Storage Requirements: Kits should be stored in the dark and at room temperature.
Shelf Life: The nitrite Titrets kits have 2-year shelf lives.
Accuracy: Due to the non-linear nature of the test scale, the accuracy of this test varies with the location of the test result on the scale. At twice the minimum concentration for a particular
NITRITE IMPORTANCE :
Nitrite, an intermediate in the nitrogen cycle, is formed during the decomposition of organic matter but readily oxidizes to form nitrate. These processes occur in wastewater treatment plants, water distribution systems, and natural waters. Nitrites are useful as corrosion inhibitors, preservatives, pigments, and in manufacturing many organic preservative chemicals. A Maximum Contaminant Level of 1 mg/L has been established by the USEPA for nitrite-nitrogen in drinking water.
OFFER :::---
Do not forget to ask JUMBO PACK OFFER ( TK - extra pack )
BUY 2 - GET 2 FREE TK extra pack
TIPS for estimation of Total Dissolved solids in water:
Requirements: Glass and plastic beaker Spirit lamp
Funnel and filter paper Boiling chips
Procedure:
. Filter the sample water.
. Weigh the glass beaker W1 g
. Take 50 mL of sample water in the glass beaker.
. Evaporate the water carefully until the glass beaker becomes dry.
. Cool and weigh the glass beaker with the boiling chips again, W2 g.
Calculation: Total solid (ppm) = (W1 – W2) x 2 x 104 Filterable residue:
Procedure:
. Weigh the empty glass beaker with boiling chips, W1 g.
. Filter the sample water into a plastic beaker.
. Pour 50 mL of filtered water into the glass beaker.
. Evaporate the water carefully until the glass beaker becomes dry.
. Cool and weigh the glass beaker with the boiling chips again, W2 g.
Calculation:
Filterable residue (ppm) (W2 – W1) x 2 x 104
Non-filterable residue (ppm) = total solid – filterable residue.
#NitriteTestKit_ManufacturerSupplier
#NitriteTestKit_IndiaUAEoman
Nitrite Test Kit manufacturer supplier distributor in Mumbai, Kandla, Kolkata, Vizag, Chennai, India, Fujairah, Dubai UAE, Muscat Oman, Kenya Africa. Get the best quality of Nitrite Test Kit at a competitive price from us. We have ready stock of Nitrite Test Kit in India, UAE Gulf, Oman, Kenya Africa. Contact us for bulk as well as small orders.